我是靠谱客的博主 忧郁火,最近开发中收集的这篇文章主要介绍python modbus tk 库_主流modbus python库比较,觉得挺不错的,现在分享给大家,希望可以做个参考。

概述

主流modbus python库比较

主流modbus python库

比较

minimalmodbus 使用

主流modbus python库

当前,用的比较多的Modbus python 库主要有以下几种:

Modbus_tk

Pymodbus

Minimalmodbus

Umodbus

比较

库名称

安装

源码

3rd party依赖

主要功能

modbus_tk

pip install modbus_tk

https://github.com/ljean/modbus-tk

pyserial

Support modbus TCP and RTU, both master and slave。Don’t support modbus ASCII。 重量级

pymodbus

pip install pymodbus

https://github.com/riptideio/pymodbus/

pyserial

Support modbus TCP/RTU/ASCII, master and slave。 重量级

minimalmodbus

pip install minimalmodbus

https://github.com/pyhys/minimalmodbus

pyserial

Only support Modbus RTU and ASCII, and only work in master(clinet). 非常轻量级

uModbus

pip install uModbus

https://github.com/AdvancedClimateSystems/uModbus/

no

Support both Modbus client amd server (both TCP and RTU). Don’t support Modbus ASCII。轻量级

minimalmodbus 使用

Doc:

https://minimalmodbus.readthedocs.io/en/stable/

https://pypi.org/project/minimalmodbus/

API https://minimalmodbus.readthedocs.io/en/stable/apiminimalmodbus.html

read_register(registeraddress, number_of_decimals=0, functioncode=3, signed=False)[source]

Read an integer from one 16-bit register in the slave, possibly scaling it.

The slave register can hold integer values in the range 0 to 65535 (“Unsigned INT16”).

Args:

• registeraddress (int): The slave register address (use decimal numbers, not hex).

• number_of_decimals (int): The number of decimals for content conversion.

• functioncode (int): Modbus function code. Can be 3 or 4.

• signed (bool): Whether the data should be interpreted as unsigned or signed.

Note

The parameter number_of_decimals was named numberOfDecimals before MinimalModbus 1.0

If a value of 77.0 is stored internally in the slave register as 770, then use number_of_decimals=1 which will divide the received data by 10 before returning the value.

Similarly number_of_decimals=2 will divide the received data by 100 before returning the value.

Some manufacturers allow negative values for some registers. Instead of an allowed integer range 0 to 65535, a range -32768 to 32767 is allowed. This is implemented as any received value in the upper range (32768 to 65535) is interpreted as negative value (in the range -32768 to -1).

Use the parameter signed=True if reading from a register that can hold negative values. Then upper range data will be automatically converted into negative return values (two’s complement).

signed Data type in slave Alternative name Range

False Unsigned INT16 Unsigned short 0 to 65535

True INT16 Short -32768 to 32767

Returns:

The register data in numerical value (int or float).

Raises:

TypeError, ValueError, ModbusException, serial.SerialException (inherited from IOError)

write_register(registeraddress, value, number_of_decimals=0, functioncode=16, signed=False)[source]

Write an integer to one 16-bit register in the slave, possibly scaling it.

The slave register can hold integer values in the range 0 to 65535 (“Unsigned INT16”).

Args:

• registeraddress (int): The slave register address (use decimal numbers, not hex).

• value (int or float): The value to store in the slave register (might be scaled before sending).

• number_of_decimals (int): The number of decimals for content conversion.

• functioncode (int): Modbus function code. Can be 6 or 16.

• signed (bool): Whether the data should be interpreted as unsigned or signed.

Note

The parameter number_of_decimals was named numberOfDecimals before MinimalModbus 1.0

To store for example value=77.0, use number_of_decimals=1 if the slave register will hold it as 770 internally. This will multiply value by 10 before sending it to the slave register.

Similarly number_of_decimals=2 will multiply value by 100 before sending it to the slave register.

As the largest number that can be written to a register is 0xFFFF = 65535, the value and number_of_decimals should max be 65535 when combined. So when using number_of_decimals=3 the maximum value is 65.535.

For discussion on negative values, the range and on alternative names, see read_register().

Use the parameter signed=True if writing to a register that can hold negative values. Then negative input will be automatically converted into upper range data (two’s complement).

Returns:

None

Raises:

TypeError, ValueError, ModbusException, serial.SerialException (inherited from IOError)

最后

以上就是忧郁火为你收集整理的python modbus tk 库_主流modbus python库比较的全部内容,希望文章能够帮你解决python modbus tk 库_主流modbus python库比较所遇到的程序开发问题。

如果觉得靠谱客网站的内容还不错,欢迎将靠谱客网站推荐给程序员好友。

本图文内容来源于网友提供,作为学习参考使用,或来自网络收集整理,版权属于原作者所有。
点赞(36)

评论列表共有 0 条评论

立即
投稿
返回
顶部